E-HOUSE
The electrical house, a prefabricated modular outdoor integrated power distribution facility rated 40.5 kV and below, adopts a container‑style steel compartment. All systems including switchgear, reactive power compensation, UPS, metering, protection, measurement &control, HVAC, fire protection, lighting and monitoring are fully assembled and commissioned in factory.
Featuring high integration, mobility and fast deployment without dedicated equipment rooms, it can go live on site after hoisting and interface connection, cutting construction cycles and civil engineering costs. With IP54 or higher protection and -40℃~+55℃ operating temperature range, it supplies safe, stable and smart power distribution solutions for data centers, industrial parks, municipal projects, construction sites and emergency power supply scenarios.
Product Features
Superior Build Quality: Constructed from high strength weather resistant steel, it delivers earthquake resistance, fire safety, thermal insulation and rain proof performance, featuring long service life and maintenance free operation.
Cost Savings: Standardized design, factory fabrication and modular assembly reduce construction complexity and cut project costs.
High Flexibility: The compact, well planned and harmonized overall layout allows flexible configuration adjustment per client requirements, facilitating later stage expansion and modification.
Fast Delivery: 3 month in factory production cycle plus 1 month on site installation period.
Small Footprint: Occupies 30%~70% less land area compared with conventional civil engineered substations.
Technical Parameter
| Environment conditions | ||||||
| Ambient air temperature | Maximum temperature | 50℃ | ||||
| Minimum temperature | -25℃ | |||||
| Daily average temperature | 25~30℃ | |||||
| Ambient humidity | Daily mean relative humidity | ≤95% | ||||
| Monthly meanrelativehumidity | 20% ~ 80% | |||||
| Wind pressure | ≤700Pa (equivalent to a wind speed of 34 m/s) | |||||
| Seismic intensity | Not exceeding magnitude 8 | |||||
| Equipment derating basis | 40℃ | |||||
| Altitude of the installation site | ≤1000m | |||||
| Sunshine/UV Radiation | 1200 W/m² | |||||
| Typical specification | ||||||
| Strength | Top load: ≥2.5 kN/m²; Top load‑bearing capacity of steel structure: 0.85 kN/m² | |||||
| Mechanical impact resistance:IK10 | ||||||
| Corrosion Protection | Corrosion‑free service life 40 years in C4 environment | |||||
| thermal insulation | Steel plate thickness: ≥2 mm; | |||||
| Thermal conductivity: ≤0.034 W/m·K | ||||||
| IP Rating | ≥IP55,Capable of long‑term operation protection in desert regions. | |||||
| Ventilation | Normal operating condition: Air change rate inside the compartment ≥ 6 times/h; | |||||
| Emergency ventilation: Air change rate inside the compartment ≥ 12 times/h | ||||||
| Fire Resistance | Class‑A fire‑resistant structure | |||||